Products

– IPPL4F

IPPL4F

IPPL4F model Industrial Positive Pressure is a double wall stainless steel chimney with 4″ ceramic insulation.
Documents
Data sheets
Features
  • Inner wall: 316L or 304 2B stainless steel (20 ga – 6” (152 mm) to 40” (1016 mm) diameter; 18 ga – 42” (1067 mm) to 48” (1219 mm) diameter).
  • Outer wall: 301, 430, 316L, 304 2B stailess steel or galvalume (24 ga – 6” (152 mm) diameter; 20 ga – 42” (1067 mm) to 48” (1219 mm) diameter).
  • Continuous laser welding
  • Full range of accessories including elbows, fittings, guides and supports.
Weights and Clearances
IPPL4F LINEAR WIEGHT
I.D O.D AREA IPPL4F
in mm in mm in2 mm2 lb/ft kg/m
6 152 14 356 28 18.2 14.6 21.8
8 203 16 406 50 32.4 17.7 26.3
10 254 18 457 79 50.7 20.7 30.8
12 305 20 508 113 73 23.8 35.4
14 356 22 559 154 99.3 26.8 39.9
16 406 24 610 201 129.7 29.9 44.4
18 457 26 660 254 164.2 32.9 49
20 508 28 711 314 202.7 35.9 53.5
22 559 30 762 380 245.2 39 58
24 610 32 813 452 291.9 42 62.5
26 660 34 864 531 342.5 45.1 67.1
28 711 36 914 616 397.3 48.1 71.6
30 762 38 965 707 456 51.2 76.1
32 813 40 1016 804 518.9 54.2 30.7
34 864 42 1067 908 585.8 57.3 35.2
36 914 44 1118 1018 656.7 60.3 89.7
38 965 46 1168 1134 731.7 63.3 94.3
40 1016 48 1219 1257 810.7 66.3 98.8
42 1067 50 1270 1385 893.8 83.3 124
44 1118 52 1321 1521 981 87 129.4
46 1168 54 1372 1662 1072.2 90.6 134.9
48 1219 56 1422 1810 1167.5 94.3 140.3
MINIMUM CLEARANCE AIR SPACE TO COMBUSTIBLE CONSTRUCTION
MODEL IPPL4F
Inside diameter Clearance
(1000ºF) (1000ºF et 1400ºF)
6'' to 12'' 1''
14'' 1.5"
16'' to 18'' 2"
20'' to 22'' 3''
24'' to 26'' 4''
28'' to 32'' 5''
34'' to 36'' 6''
38'' to 40'' 7''
42'' to 48'' 8''
Listing
Applications
  1. Building Heating Appliance Chimney Listing (1000°F Chimney Listing) under this category, models IPPL, IPPL2,IPPL2F and IPPL4F, have been determined suitable for venting flue gases at a temperature not exceeding 540°C (1000°F) under continuous operating conditions, from gas, liquid, oil or solid fuel fired appliances.
  2. Building Heating Appliance Chimneys are suitable for use with Building Heating Appliances and Low Heat Appliances as described in the Chimney Selection Chart of National Fire Protection Association (NFPA) Standard No. 211.
  3. 1400°F Chimney Listing “ under this category, models IPPL, IPPL2F and IPPL4F, have been determined suitable for venting flue gases at a temperature not exceeding 760°C (1400°F) under continuous operating conditions. As such, they are suitable for use with ovens and furnaces as described in the Chimney Selection Chart of NFPA No. 211, in addition to other applications.
Criteria Grease Duct Restaurant BHA Chimney 1400°F Chimney
Application Cooking Appliances, Ventilation Hoods, Restaurant Grease Ducts & Pizza Oven Exhausts Low and High Pressure Steam Boilers, Diesel and Turbine, Exhausts & Building Heating Equipment Industrial furnaces, Processing Equipment, Kilns and Ovens, Incinerator, Coffee Roaster & Diesel and Turbine Exhaust
Continuous operating temperature 500°F 1000°F 1400°F
IPPL Yes Yes Yes
IPPL2 N/A Yes N/A
IPPL2F Yes Yes Yes
IPPL4F N/A Yes Yes