GDPL

GDPL

GDPL model Industrial Positive Pressure is a double wall grease duct system with 2″ air space.
Documents
Data sheets
Features

Inner wall: 316L or 304 2B stainless steel (20 ga – 6” (152mm) to 40” (1016mm) diameter; 18 ga – 42” (1067mm) to 48” (1219mm) diameter)

Outer wall: 301,316L, 304 2B stainless steel, 430 or galvalume(24 ga – 6” (152mm) to 40” (1016mm) diameter; 20 ga – 42” (1067mm) to 48” (1219mm) diameter)

Insulation: 2” (51mm) air space

Weights and Clearances for GDPL Series
GDPL
I.D. O.D. Area Linear Weight
in mm in mm in2 1000 mm2 lb/ft kg/m
6 152 10 254 28 18.2 5.7 8.5
8 203 12 305 50 32.4 7.2 10.8
10 254 14 356 79 50.7 8.8 13
12 302 16 406 113 73 10.3 15.3
14 356 18 457 154 99.3 11.8 17.5
16 406 20 508 201 129.7 13.3 19.8
18 457 22 559 254 164.2 14.8 22
20 508 24 610 314 202.7 16.3 24.3
22 559 26 660 380 245.2 17.8 26.5
24 610 28 711 452 291.9 19.3 28.7
26 660 30 762 531 342.5 20.8 31
28 711 32 813 616 397.3 22.3 33.2
30 762 34 864 707 456 23.8 35.5
32 813 36 914 804 518.9 25.4 37.7
34 864 38 965 908 585.8 26.9 40
36 914 40 1016 1018 656.7 28.4 42.2
38 965 42 1067 1134 731.7 29.9 44.5
40 1067 44 1118 1257 810.7 31.4 46.7
42 1067 46 1168 1385 893.8 46.2 68.7
44 1118 48 1219 1521 981 48.3 71.9
46 1168 50 1270 1662 1072.2 50.4 75
48 1219 52 1320 1810 1167.5 52.5 78.2
MINIMUM CLEARANCE AIR SPACE TO COMBUSTIBLE CONSTRUCTION
GDPL SERIES
I.D CLEARANCE
in mm in mm
6 to 14 152-355 14 355
16 to 22 406-559 16 406
24 to 32 610-813 18 457
34 to 42 864-1067 20 508
34 to 48 864-1219 20 508
Listing

CHEMINÉE LINING.E inc. venting systems models GDP, GDPL, GDPL2F and GDPL4F are listed by Underwriters Laboratories, inc. (UL) under File MH26661 and tested in accordance with UL 1978 Standard for grease ducts. These requirements cover grease ducts and grease duct assemblies that are intended to be installed with less than or greater than 18″ clearance as specified in the Standard for Removal of Smoke and Grease-Laden Vapors from Commercial Cooking Equipment, NFPA 96 or the individual listing intended for installations where the duct passes through partitions or walls of combustible material or where the duct is located in proximity to combustible building construction.

GDP, GDPL, GDPL2F AND GDPL4F SERIES Temperature SIZE
Grease Duct 550°F continuous 6" to 48" I.D.
Applications
  1. Grease duct models GDP, GDPL, GDPL2F and GDPL4F are suitable for use in installations using exhaust system components for the removal of smoke and grease laden vapors in commercial, industrial, institutional and similar type applications.
  2. Models GDP, GDPL, GDPL2F and GDPL4F grease ducts are intended for use as complete systems.
  3. They can be connected to hoods, grease extractors, upblast exhausters, in-line or utility fans used in restaurants, hotels and other food service applications. They can also serve as supply duct in make-up/exhaust type systems.
  4. Installation of GDP, GDPL, GDPL2F and GDPL4F grease ducts is made in accordance with CHEMINÉE LINING. E inc. installation instructions manual and NFPA 96 “Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations”.
  5. GDP, GDPL, GDPL2F and GDPL4F grease ducts are suitable for continuous operation at temperatures not exceeding 500°F (260°C).
CRITERIA GREASE DUCT BHA CHIMNEY 1400°F CHIMNEY
Application Cooking appliances, Ventilation hoods, Restaurant grease ducts & Pizza oven exhausts Low and high pressure steam boilers, Diesel and turbine exhausts & Building heating equipment Industrial furnaces, Processing equipment, Kilns and ovens & Diesel and turbine exhausts
Continuous operating temperature 500°F 500°F 1000°F 1400°F
GDPL YES YES YES